Specifications (Netfinity EXP15 - 3520)
Specifications
Size
- With front panel:
- Depth: 57.9 cm (22.8 in.)
- Height: 13.2 cm (5.20 in.)
- Width: 48.2 mm (18.97 in.)
Weight
- Typical EXP15 unit as shipped: 39.0 kg (86.0 lb)
Electrical Input
- Sine-wafe input (50 to 60 Hz)
- Low range:
Minimum: 9O Vac
Maximum: 127 Vac
- High range:
Minimum: 189 Vac
Maximum: 257 Vac
- Input Kilovolt-amperes (kVA) approximately:
- Minimum configuration:
0.06 kVA
- Maximum configuration:
0.39 kVA
Environment
- Air Flow: Air flow is from front to back
- Air temperature:
- Expansion Unit on:
10° to 35° C (50° to 95° F)
Altitude: 0 to 914 m (3000 ft.)
- Expansion Unit on:
10° to 32° C (50° to 90° F)
Altitude: 914 m to 2133 m (3000 ft. - 7000 ft.)
Heat Output
- Approximate heat output in British Thermal Units (BTU) per hour:
- Minimum configuration: 205.2 BTU (60 watts)
- Maximum configuration: 1333.8 BTU (390 watts)
Acoustical Noise Emission Values
- Sound Power (idling):
- 6.2 bels (open bay)
- 6.4 bels (typical)
- Sound Power (operating):
- 6.2 bels (open bay)
- 6.5 bels (typical)
- Sound Pressure (idling):
- 47 dBA (open bay)
- 49 dBA (typical)
- Sound Pressure (operating):
- 47 dBA (open bay)
- 50 dBA (typical)
These levels are measured in controlled acoustical environments according to ISO 7779
and are reported in accordance with ISO 9296.
The declared sound power levels indicate an upper limit, below which a large portion
of machines operate.
Sound pressure levels in your location might exceed the average 1-meter values stated
because of room reflections and other nearby noise.
Back to
More INFORMATION / HELP is available at the IBM-HelpCenter
Please see the LEGAL - Trademark notice.
Feel free - send a for any BUG on this page found - Thank you.